Air coolers

AVO Horizontal air coolers 2AVG TU 26-02-1158-95

Horizontal air coolers 2AVG are intended for condensation and cooling of vapor, gaseous and liquid mediums, used in technological processes of oil-refining, petrochemical and chemical industries.

Type of air cooler climatic version is UHL and T, placement category - I as per GOST 15150-69.

AVO are designed for operation at temperatures and under pressure meeting the requirements of OST 26-02-1309. It is allowed to use air coolers with design pressure more than 2,5 MPa (25 kgf/cm2) for operation under vacuum with residual pressure up to 666,6 Pa (5mm of mercury column).

Air cooler sections are designed for cooling liquids with outlet viscosity up to 5,10-5 m2/с (50 cSt).

Metal carcass is designed to be used in regions with seismicity up to magnitude 7 and wind velocity head meeting the requirements of geographical region IV.

Technical characteristics of horizontal air cooler 2AVG:

Heat-exchange surface, m2

from 765 to 4710

Finned surface factor

9 and 20

Length of finned tubes, m

4 and 8

Number of tube rows

4, 6

Number of passes in tube space

1, 2, 3, 4, 6

Rated pressure, MPa

0,6; 1,6; 2,5; 4,0; 6,3

Material

Carbon steel; stainless steel; brass

Fan

Axial

-         fan wheel diameter, mm

2800

-         rotation frequency , rev/min

425

-         number of fans in air cooler, pc.

1 or 2

Electric motor drive VASО2-30(22)-14

 

-         implosion protection

1ExdIIBT4

-         rated power of one electric motor, kW

22; 30